Note for Maximum Number of Devices Version 1.10
Maximum Number of Network Slave products is 64 (in addition to the Master):
The following equations also need to be satisfied:
(1*a) + (2*b) + (3*c) + (4*d) ≦ 64
a: Number of slave products that occupy 1 station
b: Number of slave products that occupy 2 stations
c: Number of slave products that occupy 3 stations
d: Number of slave products that occupy 4 stations
(16*A) + (54*B) + (88*C) ≦ 2304
A: Number of Remote I/O products
B: Number of Remote Device products
C: Number of Local Stations and Intelligent Device products
Local Station includes Standby Master station
TOP↑
Note for Maximum Number of Devices Version 2.0
Maximum Number of Network Slave products is 64 (in addition to the Master):
The following equations also need to be satisfied:
(a + a2 + a4 + a8) +
(b + b2 + b4 + b8)*2 +
(c + c2 + c4 + c8)*3 +
(d + d2 + d4 + d8)*4 ≦ 64
(a*32 + a2*32 + a4*64 + a8*128) +
(b*64 + b2*96 + b4*192 + b8*384) +
(c*96 + c2*160 + c4*320 + c8*640) +
(d*128 + d2*224 + d4*448 + d8*896) ≦ 819
(a*4 + a2*8 + a4*16 + a8*32) +
(b*8 + b2*16 + b4*32 + b8*64) +
(c*12 + c2*24 + c4*48 + c8*96) +
(d*16 + d2*32 + d4*64 + d8*128) ≦ 2048
a: Number of units with 1 occupied station & 1 time setting
b: Number of units with 2 occupied stations & 1 time setting
c: Number of units with 3 occupied stations & 1 time setting
d: Number of units with 4 occupied stations & 1 time setting
a2: Number of units with 1 occupied station & 2 times setting
b2: Number of units with 2 occupied stations & 2 times setting
c2: Number of units with 3 occupied stations & 2 times setting
d2: Number of units with 4 occupied stations & 2 times setting
a4: Number of units with 1 occupied station & 4 times setting
b4: Number of units with 2 occupied stations & 4 times setting
c4: Number of units with 3 occupied stations & 4 times setting
d4: Number of units with 4 occupied stations & 4 times setting
a8: Number of units with 1 occupied station & 8 times setting
b8: Number of units with 2 occupied stations & 8 times setting
c8: Number of units with 3 occupied stations & 8 times setting
d8: Number of units with 4 occupied stations & 8 times setting
(16*A) + (54*B) + (88*C) ≦ 2304
A: Number of Remote I/O products
B: Number of Remote Device products
C: Number of Local Stations and Intelligent Device products
Local Station includes Standby Master station
TOP↑